DIMENSIONS: |
40 1/4"
L x 31" W x 72 1/4" H |
WEIGHT: |
368 lbs.
installed
440 lbs. shipping weight |
CABINET: |
16 gauge
galvanized welded steel cabinet with baked enamel and drain connection for
oil mist removal. Four heavy duty swivel casters. |
POWER INPUT: |
Voltage |
Phase |
1 HP Amps |
2 HP Amps |
3 HP Amps |
110-120 |
1 |
12 |
NA |
NA |
208-240 |
1 |
6.6 |
9 |
NA |
208-240 |
3 |
3.8 |
7 |
9 |
440-480 |
3 |
1.9 |
3.5 |
4.4 |
|
PRIMARY FILTER: |
24" x
24" x 22" 8 pocket, 66 sq. ft. of synthetic media.
Optional filters can increase filter media to 200 sq. ft. |
AIRFLOW/EFFICIENCY: |
Stock # |
Filter |
CFM=Cubic Feet Per Minute Per Arm |
1 HP |
2 HP |
3 HP |
1 Arm |
2 Arm |
1 Arm |
2 Arm |
1 Arm |
2 Arm |
41072 |
95% Bag |
1155 |
865 |
1575 |
1050 |
1665 |
1245 |
41056 |
85% Bag |
1170 |
870 |
1595 |
1065 |
1675 |
1260 |
41055 |
65% Bag |
1175 |
915 |
1600 |
1115 |
1700 |
1320 |
41057 |
50% Bag |
1190 |
955 |
1620 |
1170 |
1725 |
1375 |
41061 |
35% Bag |
1200 |
1000 |
1635 |
1195 |
1775 |
1390 |
|
PREFILTER: |
30-35%
efficient pleated filter, 24" x 24" x 4". Filter media is a cotton and
synthetic blend. Total prefilter media area is 29.5 sq. ft. |
MOTOR: |
1 HP
sealed ball bearings and thermally protected. Adjustable motor sheave
allows for field adjustments to the rated air flow. |
BLOWER: |
Forward
curved, ball bearing, belt driven centrifugal blower. This blower is
capable of moving 4400 cfm free air. |
INSTRUMENTATION: |
Dirty Filter Gage — Factory installed pressure gage
designed to determine filter replace ment cycle.
Indicator Light — Light indicates that the blower
motor is energized properly. |
FILTER ACCESS: |
Side
load track system with hinged access door. |
SOUND LEVELS: |
67 dBA
at 9’, 66 dBA at 15’. |
MECHANICAL ARM: |
10’
externally supported arm swings 180° on its axis and reaches from floor to
11’. high. Once this arm is positioned, the hood and hose remain in place
until moved. |